09 Oct Your generator has one job this summer. Make sure it can do it.
Most generators that let people down in summer aren’t faulty. They’ve sat for a year with old fuel, a tired battery and a radiator full of dust, and nobody has run them under real load. All of that can be fixed in October for not much money. In January, with the power out and stock needing water, it’s a different story.
Need some more advice?
START WITH THE FUEL
If I could only check one thing on a standby set, it would be the fuel. Diesel doesn’t keep forever. In a clean, cool, full tank you might get a year out of it. In a half-empty tank sitting in the sun, a lot less.
A half-empty tank breathes. It pulls in warm air during the day, and overnight the moisture condenses on the tank walls and runs to the bottom. Diesel bug lives where that water meets the fuel. It’s a microbial growth that turns into dark slime, and it blocks filters fast.
Older engines would put up with a bit of rubbish in the fuel. Common rail won’t. The clearances inside a modern injector or pump are a few microns, and water or grit that gets past the filter does expensive damage.
What to do about it:
- Check your bulk tank as well. Clean fuel in the generator doesn’t help if you’re topping it up from a contaminated tank.
- Drain the water separator and the bottom of the tank. If water or dark sludge comes out, deal with it now.
- Keep the tank full over summer. Less air space means less condensation.
- If the fuel is more than a year old, or smells off or looks cloudy, replace it. Put the old stuff through a tractor that’s working every day, if it’s clean.
- If you find bug, a biocide will kill it, but the dead growth still has to go somewhere. Expect to change filters once or twice afterwards.
- Fit new fuel filters before summer, and keep at least two spare sets.
BATTERIES
A flat or weak battery is the most common reason a standby set won’t start. Heat is hard on batteries, and one that sits unused slowly discharges.
- If the battery is more than three or four years old, replace it. A new battery is cheap next to a shed full of dead birds.
- A voltmeter reading doesn’t tell you much. Get it load tested.
- Clean and tighten the terminals.
- Fit a float charger if the set doesn’t have one, and check that it’s actually working.
- Keep a jump pack or a set of leads within reach of the generator.
RUN IT UNDER REAL LOAD
Starting the generator once a month and letting it idle for five minutes proves it starts. It doesn’t prove it will carry your pumps and coolroom for three days.
Short runs with no load are also bad for the engine. It never gets up to temperature, so unburnt fuel and carbon build up in the cylinders and exhaust. Do that for long enough and you get a set that smokes, uses oil and is down on power when you need it.
Once a month, run it for at least half an hour with real load on it. Aim for half its rated output or more. Before summer, do one proper test:
- Switch over to the generator the way you would in an outage.
- Start everything you’d need to run, in the order you’d start it.
- Leave it running for a couple of hours in the heat of the day.
- Watch the temperature, oil pressure, voltage and frequency.
- Walk around it. Look for leaks, loose connections, and belts or hoses that are past it.
If something is going to trip, overheat or leak, you want to find out on a day when the grid is still there.
HEAT
Generators make less power in extreme heat. Every set is rated at a certain ambient temperature, and above that the output drops. The spec sheet will tell you by how much. If your set is only just big enough at 25 degrees, it isn’t big enough at 45.
The cooling system is where most heat problems start.
- Blow the radiator out with compressed air, from the opposite side to normal airflow. Go easy on the pressure. A pressure washer up close will flatten the fins.
- Check the coolant level and condition. If it’s rusty or you can’t remember when it was changed, change it.
- Squeeze the hoses. Soft, swollen or cracked ones get replaced. Check the fan belt for cracks and tension.
- Look at where the set lives. A closed tin shed turns into an oven. The hot air off the radiator has to get out of the building, and cool air has to get in.
- Shade helps, as long as you don’t block the airflow to get it.
In dust, check the air filter more often. Go by the restriction indicator if there’s one fitted. Don’t keep blowing out a paper element with compressed air. It damages the paper and lets dust straight through to the engine. Keep a spare and swap it.
KNOW HOW LONG YOU CAN RUN IT
Ask most people how many days of fuel they have and you’ll get a guess. Work it out properly.
As a rough guide, a diesel generator burns about 0.3 litres an hour for every kilowatt of load. Your set’s data sheet will have the exact figures.
Say you’re pulling 12 kW around the clock:
- 12 kW x 0.3 = about 3.6 litres an hour
- 3.6 x 24 = about 86 litres a day
- A 200 litre drum lasts a bit over two days
After a fire or a big storm, outages at the end of a rural line can run to several days. Roads may be closed and the fuel truck may not get through. Decide how many days you need to cover, then check that the fuel on site matches.
You can stretch it. Work out which loads have to run constantly and which can be cycled. A coolroom that’s kept shut will hold temperature for a while with the compressor off. A ventilated poultry shed won’t.
SIZE AND CONNECTION
Adding up the running watts of everything you own will give you the wrong answer. Electric motors are the catch. A pump or compressor motor started direct on line can pull around six times its running current for the first few seconds.
A set that runs your loads comfortably can still stall or trip when a big pump kicks in on top of everything else.
- Start the biggest motor first, while the generator has the most headroom.
- Bring the other loads on one at a time. Don’t throw the main switch with everything turned on.
- If one large motor is the problem, a soft starter or variable speed drive is often cheaper than a bigger generator.
- Write the start order down and tape it up next to the set. The person starting it at 2am might not be you.
Have a licensed electrician fit a proper changeover switch. Never backfeed through a power point or a homemade lead. It sends power back up the line, and it can kill the linesman working to get you reconnected.
One more that catches people out every year. Standard grid-connected solar shuts down when the grid goes down. Unless you have batteries and an inverter set up for backup, your panels will do nothing in an outage.
WHAT TO KEEP ON THE SHELF
When it’s 44 degrees and half the district has no power, parts are hard to get and so are mechanics. Keep the basics with the generator:
- Two sets of fuel filters
- Engine oil and an oil filter
- An air filter
- A fan belt
- Coolant
- A jump pack or leads
- The manual, with the service intervals marked
A standby set might do 20 hours in a normal year. A week of continuous running is 168 hours. Some smaller sets need an oil change every 100 to 250 hours, so a long outage can take you past a service. Check the oil every day it’s running, and keep a note of the hours.
THE ONE-HOUR CHECK
If you do nothing else before summer, do this:
- Drain the water separator and check what comes out.
- Check the age of the fuel and fill the tank.
- Change the fuel filters.
- Load test the battery and clean the terminals.
- Blow out the radiator and check coolant, hoses and belt.
- Check the air filter.
- Check the oil level and when it was last changed.
- Run the set under real load for a couple of hours on a hot day.
- Work out your fuel in days.
- Write down the start order and put it where people will see it.
None of this is complicated, and most of it you can do yourself. If you find something you’re not sure about, get a diesel mechanic to look at it now. Whoever you use will have a lot more time for you in October than in the middle of a heatwave.
I’ve put all of this on a one-page checklist. DOWNLOAD the generator summer checklist, print it, tick it off as you go and tape it up next to the set. Or view it online HERE.
Gary, Head Engineer